CCD-102/4/8/12

Error message

Deprecated function: The each() function is deprecated. This message will be suppressed on further calls in _taxonomy_menu_trails_menu_breadcrumb_alter() (line 436 of /home/komelco/public_html/sites/all/modules/taxonomy_menu_trails/taxonomy_menu_trails.inc).

Konvencionalne protivpožarne centrale

Modeli:

CCD-102 (SA DVE ZONE)

CCD-104 (ČETIRI ZONE)

CCD-108 (OSAM ZONA)

CCD-112 (DVANAEST ZONA)

Control Panel
Power supply: 90 - 264VAC
Battery capacity: 2 x 2.3Ah / 2 x 7.5Ah
Zones:
   Max. alarm current consumption: 82 mA
   Max. quiescent current consumption: 3.5 mA
   Max. detectors per zone: 32
   Max. cable resistance per zone: 44 Ohms
Sounder output:
    Maximum load: 500 mA per output
    Delay configuration: from 0 to 10 minutes
Free contact relay output: 10A to 30VCC
24V auxiliary output: 500 mA
24V resettable output:
    Maximum load: 500 mA (2)
    Replacement time: 5 seconds
Environment
Operating temperature: From -5ºC to +40ºC
Relative humidity: 95% without condensation
IP Index: IP30

Physical features
Size: 443 mm x 268 mm x 109 mm
Size with packaging: 480 mm x 310 mm x 200 mm
Weight (without batteries): 1,9 Kg

Approvals
EN54-2 and EN54-4
Certificate number: 0370-CPD-0858